The EM133 can serve any application from residential energy metering, through industrial energy and harmonic analysis through utility comprehensive substation automation. It provides multifunctional 3‑phase power metering, revenue metering and basic power quality information. The EM133 features an internal real time clock (RTC), battery backup and onboard non-volatile memory for event and data logging. The device includes 16 set points and 4 counters that operate the built in 2 DI/ 1RO or the various analog and digital I/O add-ons.
The EM133 offers a wide range of network configurations and versatile voltage and current connections: 57 to 400V AC, up to 100A direct current measurement, connection of standard CTs (1A, 5A) and a wide range of remote HACS - High Accuracy Current Sensors (split or solid cores).
Environmental Conditions | Operational ambient temperature limit range: | –25°C to +60°C |
| Specified ambient temperature range: | Specified ambient temperature range: |
| Long-term damp heat withstand according to IEC 68-2-3 | |
| Transport and storage temperature range: | –30°C to +85 °C |
| IEC 60068-2-6, AS 60068-2-6 [18]: Vibration | |
| Frequency range: | 10Hz to 150Hz |
| Vibration time (each axis): | 75 min |
| Sweep rate: | 1 oct/min |
| Max Vibration level: | 10 m/s2 (1g), f > 60Hz |
| IEC 60068-2-27, AS 60068-2-27 [19]: Shock | |
| Shock level: | 30 g |
| Time duration: | 18 ms |
| Shape: | Half sine |
| Number of shocks: | 18 |
Construction | Case enclosure: | Reinforced Polycarbonate |
| Packaging case: | Carton and Stratocell® (Polyethylene Foam) brackets |
| Labels: | Polyester film (UL94-V0) |
Three Phase Power Supply – EM133-SE (Y &D) | Indirect Connection or Direct Connection using HACS | |
| Rated input from 1, 2 or 3 phases: | 3 x 120/207-277/480 VAC 50/60Hz |
| Burden 2VA per phase | |
| Rated input from 1, 2 or 3 phases: | 3 x 120/207-230/400 VAC 50/60Hz |
| Isolation: | Input to ground: 4000V AC |
Auxiliary Power Supply – EM132-133 | Rated input: | 40-300VAC 50/60Hz, 40-300VDC, Burden 5VA |
| Frequency range operation 25-400 Hz | |
| Isolation: | Input to ground: 4000V AC |
Input Ratings | Voltage Inputs – Installation category III Model with 3 Phase Power Supply – EM133-SE (Y &D) | |
| Operating range: | 120/207V to 277/480VAC for 1A/5A/RS5 models |
| Operating range: | 120/207V to 230/400VAC for HACS models |
| Frequency range measurement 50-60 Hz | |
| Burden for 277V: | < 1.5 VA |
| Burden for 120V: | < 2 VA |
| Model with Aux. Power Supply – EM132-133 | |
| Operating range: | up to 400/690 VAC |
| Measurement range: | direct input and input via PT up to 828VAC line-toline, up to 480VAC line-to-neutral |
| Frequency range measurement 25-400 Hz | |
| Burden for 400V: | < 0.4 VA |
| Burden for 120V: | < 0.04 VA |
| Over-voltage withstands: | 1000 VAC continuous, 2000 VAC for 1 second |
| Input impedance: | 1000 kW |
| Current Inputs (via CT) – Installation category III | |
| Galvanic isolation: | 4000V AC |
| 5A secondary (standard) | |
| Current rating: | 5A RMS |
| Maximum continuous current: | 10A RMS |
| Frequency range measurement 25-400 Hz | |
| Burden: | < 0.2 VA @ In=5A |
| Overload withstanding: | 15A RMS continuous, 300A RMS for 1 second |
| 1A secondary (1A option) | |
| Current rating: | 1A RMS |
| Maximum continuous current: | 2A RMS |
| Frequency range measurement 25-400 Hz | |
| Burden: | < 0.02 VA @ In=1A |
| Overload withstanding: | 3A RMS continuous, 80A RMS for 1 second |
| 50A direct (100A option) | |
| Current rating: | 50A RMS |
| Maximum continuous current: | 100A RMS @ 55°C ambient temperature |
| Maximum continuous current: | 60A RMS @ 60°C ambient temperature |
| Frequency range measurement 25-400 Hz up to 50A | |
| Burden: | < 0.02 VA @ In=50A |
| Overload withstanding: | 100A RMS continuous @ 55°C, 2500A RMS for 1 second |
| 40mA secondary – with HACS (external CT option) | |
| External CT Operating range: | continuous 100-1200A RMS |
| Frequency range measurement 50-60 Hz | |
| 5mA secondary – with external CT (RS5 option) | |
| Operating range: | continuous 10A RMS |
| Frequency range measurement 50-60 Hz | |
| Burden: | < 0.2 VA @ In=5A |
| Overload withstanding: | 15A RMS continuous, 300A RMS for 1 second |
| Sampling Rate measurement | 128 samples per cycle |
Relay Outputs | Solid State relay standard 1 relay rated at 0.15A/24V AC/DC, 1 contact (SPST Form A) | |
| Galvanic isolation: | 4000V AC 1 min |
| Operate time: | 1 ms max. |
| Release time: | 0.25 ms max |
| Update time: | 1 cycle |
| Electromechanical relay - DRY contact, option (4DI/2DO and 12DI/4DO Optional modules) | |
| 2 or 4 relays rated at 5A/250V AC; 5A/30V DC, 1 contact (SPST Form A) Galvanic isolation: | |
| Between contacts and coil: | 3000V AC 1 min |
| Between open contacts: | 750V AC |
| Operate time: | 10 ms max |
| Release time: | 5 ms max. |
| Update time: | 1 cycle |
| Solid State relay option (4DI/2DO Optional module) 2 relays rated at 0.15A/250V AC/DC, 1 contact (SPST Form A) | |
| Galvanic isolation: | 3750V AC 1 min |
| Operate time: | 1 ms max. |
| Release time: | 0.25 ms max |
| Update time: | 1 cycle |
| Connector type: | removable, 4 pins. |
Digital Inputs | Digital Input (standard) 1 Digital Inputs Dry Contacts, internally wetted @ 5VDC | |
| Sensitivity: | Open @ input resistance >100 kW, Closed @ Input resistance < 100 W |
| Galvanic isolation: | 4000V AC 1 min |
| Internal power supply: | 5VDC |
| Scan time: | 1 ms |
| Digital Input (option) 4 Digital Inputs Dry Contacts, internally wetted @ 24VDC (4DI/2DO Optional module) | |
| Sensitivity: | Open @ input resistance >100 kW, Closed @ Input resistance < 100 W |
| Galvanic isolation: | 3750V AC 1 min |
| Internal power supply: | 24V DC |
| Scan time: | 1 ms |
| Connector type: | removable, 5 pins |
| 8 Digital Inputs Dry Contacts, internally wetted @ 24VDC (8DI Optional module) | |
| Sensitivity: | Open @ input resistance >100 kW, Closed @ Input resistance < 100 W |
| Galvanic isolation: | 3750V AC 1 min |
| Internal power supply: | 24V DC |
| Scan time: | 1 ms |
| Connectors type: | removable, 4 and 5 pins |
| 12 Digital Inputs Dry Contacts (12DI/4DO Optional module) | |
| Galvanic isolation: | 2500V AC 1 min |
| Scan time: | 1 ms |
| Connector type: | removable, 5 pins. |
| Internally/externally wetted @ 24VDC - option 1/2: | Wet contact sensing: Open > 16kW, Closed < 10kW |
| Externally wetted @ 120VDC - option 3: | Wet contact sensing option 1: Open > 160kW, Closed |
| Externally wetted @ 220VDC - option 4: | Wet contact sensing option 1: Open >320kW, Closed <100kW |
Optional Analog Outputs | 4 Analog Outputs optically isolated (AO Optional module) | |
Ranges (upon order): | ±1 mA, maximum load 5 kW (100% overload) 0-20 mA, maximum load 510 W 4-20 mA, maximum load 510 W 0-1 mA, maximum load 5 k W (100% overload) | |
Isolation: | 2500V AC 1 min | |
Power supply: | internal | |
Accuracy: | 0.5% FS | |
Update time: | 1 cycle | |
Connector type: | removable, 5 pins | |
Communication Ports | COM1 (standard) RS-485 optically isolated port | |
| Isolation: | 3000V AC 1 min |
| Baud rate: | up to 115.2 kbps. |
| Protocols: | Modbus RTU, DNP3, SATEC ASCII and IEC 60870-5-101 |
| Connector type: | removable, 3 pins |
| COM2 option Ethernet Port(Optional module) Transformer-isolated 10/100BaseT Ethernet port | |
| Protocols: | MODBUS/TCP (Port 502), DNP3/TCP (Port 20000), IEC 60870-5-104 |
| Number of simultaneous connections: | 4 (2 MODBUS/TCP + 2 DNP3/TCP). |
| Connector type: | RJ45 modular. |
| PROFIBUS DP (IEC 61158) (Optional module) RS-485 optically isolated PROFIBUS interface. | |
| Connector type: | removable, 5 pins. |
| Baud rate: | 9600 bit/s – 12 Mb/s (auto detection). 32 bytes input, 32 bytes output. |
| Protocols: | PROFIBUS |
| CANopen (Optional module) RS-485 optically isolated CANopen interface. | |
| Connector type: | removable, 5 pins. |
| Protocols: | CANopen |
| RS-232/422-485 Port (Optional module) RS-232 or RS-422/485 optically isolated port | |
| Isolation: | 3000V AC 1 min |
| Baud rate: | up to 115.2 kbps. |
| Protocols: | MODBUS RTU, DNP3, and SATEC ASCII |
| Connector type: | removable, 5 pins for RS-422/485 and DB9 for RS-232. |
| COM3 (standard) Infra-Red COM port | |
Real-time Clock | Standard Meter Clock | |
Crystal Clock Accuracy: | typical error 13.15 sec per month (2.63 minutes per year) @ 25°C (±5ppm) | |
Typical clock retention time: | 15 months | |
TOU Module Meter Clock (option) | ||
Accuracy: | typical error 7 seconds per month @ 25°C (±2.5ppm) | |
Typical clock retention time: | 36 months |
-
Nhằm giúp cho trải nghiệm khách hàng luôn được tối ưu, Patek luôn chú ý đến từng nhu cầu dù nhỏ của khách hàng để hoàn thiện dịch vụ. Cung cấp đủ thông tin, tài liệu kỹ thuật về sản phẩm với ngôn ngữ Anh - Việt theo yêu cầu giúp cho khách hàng có cơ sở để quyết định nhanh chóng trong việc lựa chọn sản phẩm với độ tin cậy, đáp ứng cao cho nhu cầu, ứng dụng.
-
Ngoài ra nếu bạn đăng ký tài khoản trên website, hoặc trở thành khách mua hàng của chúng tôi thì bạn cũng có thể tiếp cận thêm nhiều nguồn tài liệu quý giá và hữu ích dành riêng.
- Trong trường hợp chưa tìm thấy tài liệu đáp ứng nhu cầu, quý khách có thể gửi yêu cầu cụ thể trong phần Hỗ trợ
-
Nếu bạn đã đăng nhập tài khoản vui lòng nhấp vào đây để đi đến phần hỗ trợ tài liệu dành riêng.
I. Tài liệu Tiếng Anh:
II. Tài liệu Tiếng Việt:
Đang cập nhật...